The SPI225 is a high current primary injection test system for all forms of high current testing required in a substation, including testing overcurrent relays, circuit breakers, motor overloads, and current transformers. A single SPI225 is designed to test low voltage molded-case circuit breakers up to a rating of 225 A.


The SPI system is the first high current test system to permit a user to type in a predetermined current and the SPI system will generate and regulate the requested high current without preheating the test sample by pulsing the output current at high currents. The SPI system also has the unique ability to turn on at the current zero crossing every time for any load by automatically adjust the output firing angle. This eliminates DC offset for every circuit breaker type and the need for the user to determine and adjust the firing angle for different loads and circuit breakers.


All SPI systems are both fully automated and/or manually controlled. The Smart Touch View Interface (STVI) gives you the ability to manually control the unit and also perform automated testing. The SPI225 can also be controlled by a PC for fully automatic testing and report generation.

Inputs

Input voltage | Input current | Frequency

Standard (N) | 115/230 ± 15 % | 15/8 A | 60/50 Hz

CE compliant (C) | 230 ± 15 % | 8 A | 60/50 Hz


Outputs

Output ranges

Continuously adjustable in three ranges to meet a variety of test circuit impedances:

25 to 500 A at 3.5 V max.

6.25 to 125 A at 14 V max.

1.25 to 25 A at 70 V max.


Output capacity

Percent rated current | Maximum time on | Maximum time off

100 % (1X) | 30 min | 30 min

200 % (2X) | 3 min | 8 min

300 % (3X) | 30 sec | 4 min

400 % (4X) | 7 sec | 2 min


Ammeter

Operating mode: Memory, continuous

Digital display: 5-digit auto ranging display

Ranges: 1.0000 A to 99.999 kA

Overall, ammeter system: Continuous ± 1 % of reading or ± 0.05 A

Accuracy: RMS pulse ± 1.5 % of reading or ± 0.075 A


Voltmeter

Digital display: 5-digit auto ranging display

Ranges: 0.01 to 600.00 V

Accuracy: ± 1 % of reading


Timer range

Digital display: 5-digit auto ranging display

Ranges: 

0.001 to 99999 seconds

0.01 to 99999 cycles

Accuracy: ± 1 % of reading


Communications port

Ethernet 

USB 2.0

Bluetooth (optional)

Share by: