MOM600A 600A Micro-ohmmeter
The MOM600A is a 600 A micro-ohmmeter designed for measure contact resistances in high voltage circuit breakers, disconnecting switches (isolators), knife-contact fuses, bus joints, line joints etc. It is incredibly tough and hardwaring, able to be used in wide range of temperatures, so if you're working in the artic or the tropics, this machine will operate just as efficiently in the field. To that end, the complete unit includes a set of highly flexible cables (including separate measurement cables) and a sturdy transport case.
Measurement
Range: 0 – 1999 μΩ
Resolution: 1 μΩ
Inaccuracy: ±1% of reading + 1 digit (at 100 – 600 A test current)
Output, 115 V model
Current: 0 – 600 A DC
Open circuit voltage: 5.2 V DC
Current shunt output:
10 mV / 100 A ±0.5%, max 60 mV out, max 10 V to protective earth (ground)
Output, 230 V model
Current: 0 – 600 A DC
Open circuit voltage: 9 V DC
Current shunt output:
10 mV / 100 A ±0.5%, max 60 mV out, max 10 V to protective earth (ground)
Max. load capacity, 115 V model (Current adjustment set to 100%)
Output current | Min. output voltage | Max. load
time | Rest time | Input current
100 A DC | 4.6 V DC | -- | -- | 8 A
300 A DC | 3.8 V DC | 1.5 min. | 15 min. | 20 A
600 A DC | 2.6 V DC | 10 s | 5 min. | 38 A
Max. load capacity, 230 V model (Current adjustment set to 100%)
Output current | Min. output voltage | Max. load
time | Rest time | Input current
100 A DC | 8.3 V DC | -- | -- | 6 A
300 A DC | 7.2 V DC | 2.5 min. | 15 min. | 16 A
600 A DC | 5.6 V DC | 15 s | 5 min. | 32 A