The DET3TC is capable of testing on-site grounds without disconnecting the utility connection. The complete kit gives you everything you need to start testing and consists of the instrument, test leads, stakes, batteries, and calibration certificate delivered in a tough polypropylene carry case. 


The DET3TC is easy to use, with a large selector switch that enables you to change between two-pole or three-pole testing, and can be operated easily with gloved hands. What's more, the design makes the fitting of shorting links for two-pole testing a thing of the past.


The earth/ground rod tester is rated to IP54, making it a hardy outdoor instrument. Using the optional clamp around the earth/ground rod connection allows the testing of the rod without the need for disconnection, leaving the earthing system intact during testing (ART). A large, clear, easy-to-read LCD display and thumb-sized test button also makes the instrument particularly suited outdoor conditions.

C spike check: Automatic

P spike check: Automatic

Noise check: Automatic

Noise rejection: 40 V peak to peak

2-wire test: Yes

3-wire test: Yes

No disconnect testing (ART): Yes, with optional MCC Clamp

Earth current range with MCC Clamp: 0.5 mA to 19.9 A

Earth current accuracy: 5% ±3 digits

Resistance range: 0.01 to 2000 Ω

Resistance accuracy: 2% ±3 digits

Earth voltage range: 0 - 100 V a.c.

Earth voltage accuracy: 2% ±2 V

Share by: