The DCM1500 is a 1500 A TRMS clamp meter that maeasures up to 1500 A AC or DC and offers 750 VAC and 1000 VDC ranges, making it ideal for use in the installation, maintenance, fault-finding, and monitoring of large AC or DC electrical systems and equipment - anywhere where there is a need to measure current, volts, resistance, and frequency.


By using True RMS measurement techniques, the DCM1500 avoids the errors that can occur when non-sinusoidal waveforms created by today’s complex loads are measured using traditional, average-sensing clamp meters.


The DCM1500 is safety rated to IEC 61010-1 CAT IV 600 V, and is drop-tested to 1.2 m onto a hard floor. The tactile barrier below the jaws of the instrument ensures a safe working distance for the operator’s hand when measuring current on live uninsulated conductors, although additional personal protection must still be used.


The instrument has a numeric displays with large clear digits complemented by a high-resolution digital bar graph, which is useful for trending and indicating fluctuations in measurements. The backlight enables you to see the screen clearly in poorly lit areas such as distribution cupboards and corners of switch rooms, and the "data-hold" feature enables you to use the instrument on hard-to-access cables, where otherwise the display may be impossible to see. The DCM1500 comes supplied with test leads, carry case, and a full 1-year manufacturer’s warranty.

AC current 

Range |  Resolution | Accuracy | Frequency response 

400 A | 0.1 A | ±(1.5% reading + 5 digits)* | 50 Hz ~ 60 Hz 

1000 A | 1 A | ±(1.9% reading + 7 digits) | 50 Hz ~ 60 Hz 

1500 A | 1 A | ±(2.5% reading + 7 digits) | 50 Hz ~ 60 Hz 

400 A | 0.1 A | ±(1.9% reading + 5 digits)* | 61Hz ~ 400 Hz 

1000 A | 1 A | ±(2.5% reading + 7 digits) | 61 Hz ~ 200Hz 

1500 A | 1 A | ±(3.0% reading + 7 digits) | 61 Hz ~ 200 Hz

Overload Protection: 1500 A rms


DC current 

Range | Resolution | Accuracy 

400 A | 0.1 A | ±(1.0% reading + 3 digits)

1000 A | 1 A | ±(1.9% reading + 7 digits) 

1500 A | 1 A | ±(2.5% reading + 7 digits) 

Over voltage protection: AC 1000 A for 1 min

Position Error: Add ±1% of LCD reading


AC voltage (auto-ranging) 

Range | Resolution | Accuracy 

400 V | 100 mV | ±(1.0% reading + 5 digits) 

750 V | 1 V | ±(1.0% reading + 5 digits) 

Over voltage protection: 750 V rms

Input Impedance: ≥1 MΩ// less than 100pF


DC voltage (auto-ranging) 

Range | Resolution | Accuracy 

400 V | 100 mV | ±(0.7% reading + 2 digits) 

1000 V | 1 V | ±(0.7% reading + 2 digits) 

Over voltage protection: 1000 V rms

Input impedance: ≥ 1 MΩ


Resistance and continuity

Range | Resolution | Accuracy 

0 – 400 Ω | 100 mΩ | ±(1.0% reading + 3 digits) 

Over voltage protection: 600 V rms

Continuity check: buzzer sounds when resistance< 30 Ω


Frequency 

Range | Resolution | Accuracy 

20 – 400 Hz | 1 Hz | ±(0.1% reading + 2 digits)

Over voltage protection: AC /DC 1000 A for 1 min

Sensitivity: 3 A rms for < 400 Hz


Share by: