The D2 and D5 Flow Monitor is the new model with microprocessor based electronics and back lit digital display.The display can be rotated 90 degrees (electronically) which makes it possible to install the monitor both vertically and horizontally in any piping system.
The D2 and D5 is equipped with a 4-20 mA output signal as well as local alarms and HART protocol. A linearization possibility of the flow curve is built in and can be programmed by the user. Also included is a re-settable flow totalizer. In order to conveniently set up a flow system at dry conditions, a simulation mode for the analogue, frequency output signal as well as HART can be activated.
'
Flow range 0,4-25,000 l min (liquid), to choose the right range, please refer to the table of measuring ranges
Flow turndown D2 and D2-LP – 1:2
D5 – 1
Wetted Material Copper alloy, painted steel.,eaworthy stainless steel 904L, stainless steel 316.
Rubber Parts M and Fluorinated rubber (FPM)
Min pressure Appr. 1 bar (14 PSI) / 0,5 bar for LP
Max pressure 16 bar (232 PSI)
Maximum temperature control unit Operating temperature -10 to 65°C
Maximum temperature pipe section -GL and –FA: -10 to 120°C
-GSS and –FSS: -10 to 250°C
Enclosure IP65
Display Backlit graphic display, electronically rotatable
90/180/270/360°
58x30 mm (2,6” FSTN)
Counter Re-settable flow volume counter
Process connections DN 15-40 BSP/NPT thread
DN 15-500 DIN/ANSI flange (wafer)
Power supply 24VDC ±0,4 V
Connection cable Shielded twisted pair, min. 0,2 mm²
Current consumption Max 50mA
Output 4-20mA, HART protocol, pulse or 200-1000Hz frequency
Alarm relays Two relay contacts, independently adjustable within the ordered flow range
Max. 50 V AC/DC. Min. 1 mA, 5 VDC
Max. switching capacity: 30 W
Accuracy ±2%F.S. (full scale)
Repeatability ±2% actual