EGIL Circuit Breaker Tester

The EGIL circuit breaker tester is intended for circuit breakers with one contact per phase. The EGIL incorporates features commonly found on more complex test systems, but is designed to be smaller, simpler to use and less expensive than other similar test sets.
The EGIL has three channels connected together on one side and two separate time channels for measuring auxiliary contacts. Events at parallel contacts are recorded and displayed simultaneously via pre-insertion resistors.
To simplify on-site connection, the EGIL comes with ready-made multi-cable sets for both the main and auxiliary contacts. Coil currents are measured automatically and presented, together with other readings, immediately after testing on the display window or via the built-in printer. Additionally, the EGIL has a built-in breaker control unit that sets the instrument automatically for the next sequential breaker operation, making it easy and intuitive to use.
Using the EGIL with the the SDRM and the SDRM accessory enables you to perform static and dynamic resistance tests and the EGIL can also be equipped with an optional USB interface for communication with a PC and the CABA Win circuit breaker analysis software.
Time measurement
Measurement time: 1 to 100 s
Resolution: 0.1 to 10 ms
Number of channels: 3 with common ground
Time base inaccuracy: 0.05% of the reading ± resolution
Status thresholds:
Closed: < 10 Ω ±20%
Resistor: 10 Ω ±20% to 3 kΩ ±20%
Open: > 3 kΩ ±20%
Open circuit voltage: 24 V ±20%
Short circuit current: 100 mA ±20%
AUX 1&2
Number of channels: 2, galvanically isolated
Contact-sensing (Dry)
Status thresholds:
Closed: < 600 Ω ±30%
Open: > 600 Ω ±30%
Open circuit voltage: 20 V ±20% DC
Short circuit current: 25 mA ±20%
Voltage sensing (Wet)
Status thresholds:
Open indication: < 8 V (polarity insensitive)
Close indication: > 13 V (polarity insensitive)
Working voltage: 250 V AC / DC
Current measurement
Range: ±25 A per channel
Resolution: 25 mA
Inaccuracy: 1% of the reading ±100 mA
Working voltage: 250 V AC / DC
Breaker operation
Sequences: C, O, C-O, O-C, O-C-O
Continuous current: 5 A
Max current: 25 A during 300 ms, rest time 1 min
Contact function: Two independent control functions
Contact characteristics: Non bouncing, closing time max. 0.1 ms
Make/Break capacity: 25 A, 250 V (AC or DC) per contact function
Start breaker operation: By rotary switch
Pulse length: Adjustable in steps of 10 ms
Pulse delay: Adjustable in steps of 10 ms
Working voltage: 250 V AC / DC