The instrument is easy to use with a large rotary selector switch and one-press test button, both of which permit operation with gloved hands. Unlike some instruments, the design negates the need for a shorting link when making two pole measurements. There are no hidden functions with the instrument: clearly labelled auxiliary controls are used to select the test frequency (94Hz, 105Hz, 111Hz and 128Hz), output voltage (50 V or 25 V where local standards apply) and to switch the backlight on or off.


The optional MCC CLAMP augments the traditional fall-of-potential measurement method with ART (Attached Rod Technique) which allows electrode testing without disconnection and also leakage

current measurements down to 1 mA. A second optional clamp, the MVC CLAMP, enables true stakeless measurements to be made in situations where driving stakes is not practical.


The clear, easy-to-read display provides excellent contrast and viewing angle making the instrument ideally suited to outdoor use. The display is backlit, extending the operational environment of the instrument to cable cellars and other dark locations.


The instrument offers a wide measurement range of 0.01 Ω a to 200 kΩ, ground noise voltage measurement from 1 V to 100 V and ground current from 1 mA to 20 A. Accurate results can be

obtained in electrically noisy environments since the instrument is capable of rejecting noise voltages of 40 V peak to peak and the user can select different test frequencies to minimise the effect of interference.

C and P spike check: Automatic

Noise check: Automatic

Noise rejection: 40V peak to peak

2-wire, 3-wire, 4-wire test: Yes


Output voltage: ±25V or ±50V at 94Hz, 105Hz, 111Hz and 128Hz

Output current: 4.5mA or 0.45mA or 0.045mA


Ground current range with clamp: 0.5mA to 19.9A

Ground current accuracy: 5% ±3 digits


Ground voltage range: 0 to 100V ac

Ground voltage accuracy: 2% ±2V


Resistance ranges

2, 3, 4 pole: 0.01 Ω to 200 kΩ

ART: 0.01 Ω to 200 kΩ

Stakeless: 0.01 Ω to 200 Ω


Resistance accuracy

2P measurements: 2% ±3 digits

3P measurements: 2% ±3 digits

4P measurements: 2% ±3 digits

ART measurements: 5% ±3 digits

Stakeless measurements: 7% ±3 digits

Share by: