DDA-3000 and DDA-6000 Universal Circuit Breaker Test Sets

The DDA-3000 and DDA-6000 universal circuit breaker test sets are designed specifically to test low voltage power and molded-case circuit breakers equipped with thermal, magnetic, or solid-state trip devices. Universal in application, the test sets will test virtually all low voltage, molded-case, and metal-clad, direct-acting AC circuit breakers and are fully compliant with NEMA AB-4 test guidelines.
The unique transformer and circuit design results in a high capacity test set in a very compact size. Advanced digital control and instrumentation provides you with the exact testing capacity. The test sets can also be used for other high current applications, such as verifying the ratio of current transformers and performing heat runs or primary injection testing of high voltage breakers and their associated protective relays.
The DDA-3000 and DDA-6000 perform their tests by simulating an overload or fault condition. Each test set is an integrated test system that provides a variable, high current output, incorporating all control circuitry and instrumentation necessary to test direct-acting circuit breakers accurately, efficiently, and safely. All DDA-3000 and DDA-6000 test sets have identical features, instrumentation, and operational characteristics. The only changes in the specifications between the units are their size, weight, and maximum output-current capacity:
- Model DDA-3000 is rated for testing breakers up to 3000 amperes
- Model DDA-6000 is rated for testing breakers up to 6000 amperes
Input
Model No. | Input Voltage (single phase) | Input Frequency | Input Current
DDA-3000 | 460 V±5% | 60 Hz | 200 A
DDA-3001 | 380 V±5% | 50 Hz | 200 A
DDA-3002 | 415 V±5% | 50 Hz | 200 A
DDA-6000 | 460 V±5% | 60 Hz | 350 A
DDA-6001 | 380 V±5% | 50 Hz | 350 A
DDA-6002 | 415 V±5% | 50 Hz | 350 A
DDA-6004 | 575 V±5% | 60 Hz | 350 A
Output
Model No. | Maximum Continuous Current
DDA-3000 | 4500 A
DDA-3001 | 4446 A
DDA-3002 | 4446 A
DDA-6000 | 6250 A
DDA-6001 | 6175 A
DDA-6002 | 6175 A
DDA-6004 | 6175 A
Model No. | Maximum Current Through A Circuit Breaker
DDA-3000 | 35,000 A
DDA-3001 | 28,000 A
DDA-3002 | 28,000 A
DDA-6000 | 60,000 A
DDA-6001 | 50,000 A
DDA-6002 | 50,000 A
DDA-6004 | 60,000 A
Model No. | Maximum Current Through A Short Circuit
DDA-3000 | 60,000 A
DDA-3001 | 48,000 A
DDA-3002 | 48,000 A
DDA-6000 | 100,000 A
DDA-6001 | 80,000 A
DDA-6002 | 80,000 A
DDA-6004 | 100,000 A
Duty Cycle: The test set will supply the rated continuous current indicated for 30 minutes, followed by 30 minutes off
Digital Ammeter
Operating Mode: Memory, Continuous
Digital Display: 5-digit display with 0.281 in. (7 mm) numerals
Ranges: 200/2000/20,000/200,000 A
Overall Ammeter System Accuracy:
Continuous ±1% of reading
Peak Pulse ±2% of reading
RMS Pulse ±1.5% of reading
Digital Timer
Digital Display: 5-digit display with 0.281 in. (7 mm) numerals
Ranges:
0.0001 to 99999 seconds
0.0001 to 99999 cycles
Accuracy: ±1% of reading
Digital Voltmeter
Operating Mode: Input voltage, Output voltage, External voltage
Digital Display: 5-digit display with 0.281 in. (7 mm) numerals
Ranges: 0 to 600 V
Accuracy: ±1% of reading